I shouldn’t have kept the $1,000,000 computer
Summary
TLDR在这段视频中,我们跟随视频制作者一起探索了如何使用一个价值百万美元的PC服务器集群,并通过一套称为WCA的先进软件将其连接起来,形成一个巨大的存储服务器。这个服务器集群不仅拥有惊人的存储容量,达到了2.2 petabytes,而且通过PCIe Gen 4存储技术,能够达到每秒数百GB的传输速度。然而,这样的高性能也带来了高能耗和高热量的问题。为了解决这个问题,视频制作者介绍了他们如何利用免费的APC Tower Coolers进行水冷系统DIY,以及如何通过一些创新的方法,比如将冷却塔变成加热塔,来同时解决服务器室的散热问题和仓库的供暖问题。整个视频充满了技术挑战和创造性的解决方案,展示了在追求高性能计算的同时,如何通过创新思维解决实际问题。
Takeaways
- 💻 视频介绍了一个价值百万美元的PC服务器集群,通过WCA软件连接,形成一个巨大的存储服务器,能够达到每秒数百GB的速度。
- 🚀 服务器集群从6台扩展到9台存储机器,提供了2.2PB的原始存储空间,几乎与主母舰上的硬盘存储量相当,但速度快了几个数量级。
- ⚡ 尽管拥有3吨的空调,服务器房间的温度仍然高达40摄氏度,这对硬件和需要在其中工作的人来说都是不利的。
- 💡 为了节省成本,他们考虑使用免费的APC Tower coolers进行水冷,而不是增加更多的空调设备。
- 🔧 他们计划使用水冷系统来冷却服务器房间,并在冬天将热量输送到仓库,以此来加热仓库。
- 🔩 在安装过程中,他们遇到了一些挑战,包括管道配件的成本高昂和安装过程中的泄漏问题。
- 🛠️ 他们使用了SharkBite快速连接配件,这是一种易于安装且有25年保修期的解决方案,尽管成本较高。
- 💡 他们还尝试了使用冷却塔来冷却服务器房间,并利用冷却塔产生的热量来加热仓库。
- 🔄 系统设计为闭环系统,但由于蒸发损失,需要定期补充冷却液。
- 🛠️ 他们使用了厕所进水阀来简化冷却系统的补水过程,而不是设计一个复杂的定制系统。
- 🔧 在安装过程中,他们意识到需要对管道和配件进行一些调整,包括重新配置管道和更换尺寸不合适的PVC管。
- 📈 通过监控软件,他们能够实时监控冷却液的流入和流出温度,以及服务器的能耗。
Q & A
什么是百万美元PC?
-百万美元PC是一个昂贵的服务器集合,通过一个名为WCA的软件连接在一起,使其能够像一个巨大的存储服务器一样运作,能够达到每秒数百吉字节的速度。
他们如何扩展存储机器以提高存储容量?
-他们从六台存储机器扩展到九台,提供了2.2拍字节的原始KOKIA,通过PCIe Gen 4存储,这几乎和他们母库中的硬盘存储一样多,但是速度快了几个数量级。
为什么服务器房间非常热?
-尽管有3吨的空调,服务器房间仍然非常热,达到了40度,这对硬件和需要在其中工作的人来说都是不利的。
他们如何使用免费的APC Tower coolers来冷却服务器房间?
-他们继承了六台APC Tower coolers,并计划使用这些冷却器进行整个服务器房间的水冷,这次他们保证会正确执行。
他们如何将冷却塔改造成既能冷却服务器房间又能加热仓库的设备?
-他们计划在冬天使用冷却塔来冷却服务器房间,并将热空气输送到仓库以加热,从而将冷却塔转变为加热塔。
为什么他们选择使用SharkBites而不是花园软管?
-尽管最初计划使用花园软管,但他们发现软管也很昂贵,而且1英寸的管道和配件不易获得且价格昂贵。SharkBites安装简便,只需将管道推入即可,且有25年的保修期,尽管价格昂贵。
他们如何确保系统不会因为蒸发而失去冷却液?
-他们使用了一个检查阀,该阀连接到房屋的水压,可以自动补充因蒸发而损失的冷却液。
他们如何通过DIY方法来解决冷却系统的安装问题?
-他们通过自行钻孔、安装接头和使用SharkBites快速连接管道来解决安装问题,尽管过程中遇到了一些挑战,例如螺纹接头的尺寸不匹配和冷却塔的放置问题。
为什么他们决定在服务器房间使用水冷而不是传统的空气冷却?
-水冷系统可以更有效地处理大量热量,尤其是在他们的百万美元PC这样高功率的服务器房间中,水冷可以提供更好的冷却效果。
他们如何测试冷却系统的实际效果?
-他们通过创建一个热通道,使用纸板来隔离热空气,然后观察服务器的进气口温度是否有所提高,以此作为温度差异的证明。
他们如何计划改进当前的冷却系统?
-他们计划将冷却系统的散热器直接安装在机架的背面,以更直接地捕获热量。此外,他们还考虑使用电动阀门和温度传感器来自动化热量的分配,以便在需要时将热量输送到仓库或外部。
Outlines
😀 百万美金PC的升级与冷却系统改造
本段落介绍了一个非常昂贵的服务器集合,称为百万美金PC,通过一个名为WCA的软件连接,使其像一个巨大的存储服务器。服务器升级后,存储设备从6台扩展到9台,提供了2.2PB的存储空间,速度极快,但也更加耗电和发热。为了冷却这些设备,他们继承了六个APC Tower冷却器,并尝试使用冷却塔来同时冷却服务器室和加热仓库。他们还讨论了水冷系统的安装和调试过程,包括使用SharkBite快速接头和其他DIY方法。
🔧 自制冷却系统的安装与测试
在这段文字中,描述了如何将冷却系统安装到位,包括将冷却塔放置在特定位置,以及如何连接管道和配件。他们讨论了冷却塔的工作原理,以及如何通过调整气流来优化冷却效果。此外,还提到了使用厕所进水阀来填充系统,以及在安装过程中遇到的一些挑战和解决方案。
🚿 解决冷却系统的泄漏问题
此段落讲述了他们如何解决冷却系统中的泄漏问题。他们使用了昂贵的非硬化硅胶来封堵泄漏,并讨论了在安装过程中遇到的一些挑战,如坦克中间部分的厚度导致的密封问题。此外,还提到了他们如何使用PVC管和配件来构建过滤器外壳,并确保系统无泄漏后再次启动。
🌡️ 测试冷却系统的效果
在这部分中,描述了测试冷却系统效果的过程。他们通过创建一个热通道,并使用纸板来隔离热空气,以提高温度差异。他们还讨论了如何使用软件工具监控冷却液的温度和流量,以及如何通过增加额外的冷却塔来提高冷却效果。
🔄 热交换器与空调系统的协同工作
本段落讨论了热交换器和空调系统如何协同工作以提高冷却效率。他们测试了在关闭空调的情况下,服务器出口空气的温度,并考虑了如何通过热交换器来冷却仓库。还提到了使用阀门和温度传感器来自动化热管理,以及如何通过软件监控系统性能。
🎉 冷却项目的成功与未来规划
在这部分中,他们总结了冷却项目的成功,并对未来的改进进行了规划。他们提到了通过增加更多的冷却塔和改进管道系统来提高冷却效果。还讨论了如何使用电动阀门和温度传感器来自动化热管理,并考虑了将热交换器安装在机械室的可能性。此外,还提到了赞助商Squarespace,并鼓励观众创建自己的网站。
Mindmap
Keywords
💡服务器集群
💡存储容量
💡热管理
💡水冷系统
💡热交换器
💡DIY方法
💡散热塔
💡热效率
💡温度控制
💡数据中心
💡热负荷
Highlights
百万美金PC升级,通过增加存储机器数量,达到了2.2 petabytes的原始存储容量。
存储服务器使用PCIe Gen 4技术,速度可达每秒数百GB。
服务器升级后,尽管有3吨的空调,但室内温度仍高达40°C。
利用免费的APC Tower coolers进行服务器房的水冷改造。
使用冷却塔在冬季同时为服务器房降温和仓库加热,实现节能。
冷却塔的安装和测试,包括热空气和冷空气的流向调整。
使用SharkBites快速接头,简化了管道连接过程。
冷却系统采用了闭环设计,通过检查阀自动补充蒸发的水量。
通过增加管道和风扇来缓解服务器房的过热问题。
使用McMaster Car的储罐和高端接头进行DIY改造。
冷却塔的安装过程中遇到泄漏问题,通过使用硅胶密封剂进行了修复。
对冷却系统的过滤器进行了重新设计和安装。
通过调整冷却塔的设置,实现了服务器房内温度的有效控制。
冷却系统与空调的协同工作,成功降低了服务器房的温度。
使用开源监控工具check MK和SNMP协议对系统进行实时监控。
考虑使用3D打印技术为服务器架制作定制的风道遮罩。
通过增加冷却塔的数量和改进风道设计,进一步提高了冷却效率。
实现了使用冷却系统在不使用空调的情况下,服务器房内温度维持在较低水平。
展示了通过技术改造,如何将一个极端的高温环境转变为一个可控和舒适的工作环境。
Transcripts
this is the million dooll PC a very
expensive collection of servers that are
linked together with an incredible piece
of software called WCA that allows them
to act like one giant storage server
with the ability to reach speeds
measured in the 100s of gigabytes per
second watch this
and damn boy wa a second that's a little
faster than it used to be that's because
the million dooll PC has
glowed up a little bit we've scaled from
six to nine storage machines giving us a
whopping 2.2 pedabytes of raw kokia
powered pcie Gen 4 storage it's almost
as much storage as we have on hard
drives in our mother Vault but orders of
magnitude faster which means it's also
really power hungry which means it's
also really hot even with 3 tons of air
conditioning in here it's still 40
flipping de which is terrible for
hardware and terrible for any humans who
need to work in here now we could add
more air conditioning but that would be
even more expensive than this already is
you know what's not expensive the not
one but six APC Tower coolers that we
inherited for free from a local data
center that's right folks we are doing
whole server room water cooling and this
time I swear we are going to do it right
so where are the plumbers well we're not
we're not really doing it right today
we'll do it right later that's fine
right we're just going to DIY that is
not what I had in mind when I sold this
to our sponsor build Redux they make it
easy to get into the world of PC gaming
just pick your games see the performance
and the pros at build Redux will build
the PC for you visit build Redux at the
link down below now under normal
circumstances you would run chilled
water in the unit in your data center
and use that chilled water to cool the
air but chilling the water costs money
and that's what we're trying to avoid
right so since we also spend money
heating our warehouse and we have so
many of these things kicking around
anyway we were thinking why not cool the
server room and heat the warehouse in
the winter turning this one into less of
a cooling tower and more of a heating
Tower yeah it was designed for that
right I mean this should work great like
in theory this is a mint plan in
practice well I guess we're about to
find out yeah in practice we have a
giant cooling tower on a forklift on a
not storage rated uh
mezzanine water's not heavy 3 2 1 oh
okay yeah that feels
great where do we want it exactly in
theory it blows hot out that side mhm so
probably pointing that way sure that
might not be intuitive because this is
obviously the front of the unit so you
would think that's where it draws air in
but in a data center deployment these
cooling towers sit in between the
servers and servers will typically pull
cold air in from the cold aisle in front
of them and then heat up the air and
blow it out the back so by having these
towers in between your servers what
happens is that hot air comes out gets
sucked into the cooling tower and then
gets blown through this Radiator in the
middle blown out the front and sucked
back into the server let's put it in the
corner pointing that way Hey Jake yeah
what I figured out what one of the
things we thought might be a temp probe
before is what it must have gotten
jostled loose at some point but these
guys right here they have little floats
on them oh they're the like the water
level they're for an excess condensation
meter yeah when you're running chilled
water through them they can start to
condensate pretty aggressively we're not
doing that so it should be fine yeah I
saw the drip trays before and I also saw
that there was rust everywhere in the
bottom of the units but I didn't realize
that that was by Design as cool as it is
is though that this unit is more intact
it also means that we haven't modified
the fittings yet so well you did such a
great job last time so uh you want to
have a chance to try to do such a great
job too oh okay boom Uno
reverse see you later before we solder
on those fittings I want to give you
guys a bit of a background the tubing
inside the unit is 1 in which is a
pretty standard size which is nice um
except what I found out getting 1in
tubing it's not that common and also all
of the fittings are very expensive and
since this is like our DIY approach even
though my original plan was to use
garden hoses uh I found out garden hoses
are really expensive so we might as well
use the stuff we're going to use in the
long term and since we're going to have
to take it down anyways we're going to
use shark bites and shark bites are
really cool they're basically like you
push the tubing in and that's all you do
it's now a fixed it's warrantied for 25
years it's it's sick they're just really
really
expensive that's smells delicious it was
taking too
long
one and a two you got to make sure it's
clean before you solder otherwise the
solder doesn't stick at least that's
what Plumbing tick Tok told me naturally
this is going to be what you'd call a
closed loop system meaning it's filled
with a certain amount of water and
closed off but only to a point when you
have Radiant Heating in your house for
instance there is some amount of
evaporative loss so you fill the coolant
up and over time slowly you lose some of
it the way that they get around that is
by using a check valve that's basically
just hooked up to your House's water
pressure which automatically as some
evaporates a little bit comes into fill
I didn't really want to do that because
I want to do it today and I'm not a
plumber but fortunately our mechanical
room is right below us and it has a hose
bib so we were like why don't we just
hook the hose bib up to the tank but
then if you just turn it on the Tank's
going to overflow and explode and
whatever it's like how can we fill a
tank I could like design a custom system
or I could just buy a toilet fill valve
we have this tank from McMaster Car
which we're going to add fittings to
with these fancy bulkhead fittings but
in the meantime this has got to come out
the bottom which means we need to drill
a
hole it just knew the job was done I bet
you this stuff is tasty there's Supply
sparingly oh oops we're putting the
threaded ones on here we'll solder those
and then twist the female shark bites on
and then the tubing can just go like
that in
theory a she's mint
Bud it occurs to me we never tested this
thing I mean we have spare parts it
would probably be faster just to pull
another one up here right Jamie oh yeah
absolutely luckily there just so happens
to be the exact plug we need right here
20 amp 120 volt we got some adapters and
extension cords from infinite cables
thanks guys pluggy
plug hey you hear that
that's the condensation pump running at
the
start that's not too loud right sounds
great it's actually not that heavy when
there's nothing in it as he struggles to
move it what's the worst that could
happen I drop the
thing mint let's go over this one more
time pump right below the reservoir that
way it gets fed directly we had a
problem trying to Prime in at Linus's
house with the pool trying to avoid that
then it will go down to the cooler come
all the way back up blah blah blah into
our heater what I'm calling it and then
out the heater into a filter before the
reservoir so we catch all the gunk
before the reservoir reservoir back to
the pump and the Vicious Cycle continues
cool are we expecting a lot of Gunk no I
feel like we should have also filtered
the water coming
in we'll put a valve down here so that
when the water comes in well at the
start we can close this and the water
will go into the reservoir which will
make it easier to bleed then once the
system is running we just open this
valve
and most of the water will just go
directly into the pump and kind of
ignore the reservoir when it's coming
back up here that way we don't have like
the full force of the pump just like
gushing into the reservoir constantly
making a bunch of noise I wish we had
like straps this Mak this much easier
unless we use the LT Cable Management
things to this metal pipe oh hell yeah
the reason that we're putting valves
here and actually at every piece is a so
we can service a piece individually you
shut off the valves and then we can take
it out and swap it or change it or
replace it whatever we're doing and B
because it's like like I said before
this is all going to get redone properly
and I want it to be easy for him to just
take apart whoa it's like it's designed
for dude it's mint male a te and a valve
and a valve yeah this isn't going to
leak no it's going to be great they're
shark
bites sick before we had this Grand idea
of water cooling the server room we
tried to mitigate this problem by adding
a duct and a fan which was pretty easy
to do because right where we are right
here is about 10 ft from the server room
and there's just a hallway so we added
like this insulated duct between and a
big fan and it did help but ultimately
once it gets up to equilibrium it wasn't
enough hey it's through oh that wasn't
even that hard huh huh mint we forgot
about the filter I realized Alex is
putting this all together I'm like oh
yeah where are we putting the filter
damn it right where Alex is
working oh no brother brother did they
sell me the mother oh my God why
didn't I check this no filter it
is since a long-term plan is to rip the
RADS out of these giant units and just
stick it right on the back of the rack
so it captures the heat directly uh I
don't care that much about where this
goes since it's probably only going to
be here for a couple months later so
we're thinking we just leave it up
against the back here that way the hot
air comes out get get sucked in on the
back and shoots out cool air in the
front and because of that we're thinking
we just leave the back door off and then
I can just pull this tubing kind
of right in there beautiful look at that
that's mint good job Alex I'm excited to
see if it leaks or not the great thing
is we won't know until it's far too late
on the bottom side yeah oh shut it off
here's the problem we're running into
this tank is thick down the middle
Middle where the seam is and when this
is sitting in here it looks good like
that except when you tighten it down
that extra material pushes it out on an
angle and now the seals can't seal I
walk back into this project and I'm
immediately told well it leaked um oh
who whoa whoa be careful there's
fittings on the bottom but we have a fix
for the leak and it's glue no not that
not that it's the the
ooo this stuff is like $40 a tube it
does not leak it's a nice non hardening
so it stays kind of plasticky and goopy
solution silicone yeah I wasn't able to
do it exactly how I was hoping because
it's still kind of cockeyed but I don't
think it's going to leak I put I put a
lot in there but I have a job for you
cool I uh spent some of your money and
got the wrong thing so we have to do it
again if I had a dollar for every time
he said that wasn't I would be able to
afford all these mistakes what are we
building uh a filter housing they sold
me the wrong size of PVC even though I
was like I just need to connect these
two things and they were like okay we're
going to give you one inch PVC because
it's one inch well it's supposed to be
inch and a quarter cool uh so I have 20t
of 1in PVC that I have no use for and
then we went to the store they were like
okay we could we can tell you this it'll
probably be long enough so you have to
cut the threads off and then cut it in
half and
hopefully that is like enough oh man
that's going to be uh you have one shot
at this don't screw it up and this is my
saw yeah look this is what the
professionals told us to buy they might
have told us the wrong thing last time
but here we are again surely that
wouldn't happen twice no got the
clamps not really what this is for but
it's working I cut off part of the
threads I sanded down the little nubbins
now they fit in here which is why I was
doing that by the way really uh oh wait
oh balls we have to cut this down the
middle too okay well um I have to go do
a conference call so what I mean you
only got one thing done and so you
didn't even get it done I don't know if
you're getting your minutely bonus
minutely
[Music]
bonus look at that worky oh nice yeah I
didn't know that this glue set up in 10
minutes there's your filter perfect
um damn it I looked in the manual for
the cooling tower things and I did
randomly stumble upon uh them mentioning
a filter and they said a 20 mesh and I
think this is 100 so it's a lot finer
should be fine as long as our pump has
enough power for it it doesn't really
matter it I mean it's not that fine yeah
also it's still it's still like a mint
for 1in tubing so it should be fine now
we just have to find out where we can
put it now we just have to pose with
it like not everyone's a poser don't
worry can you walk me through what's
going on here a little bit because I
missed the part where you guys drilled
holes in the building we've got the
cooling tower over there we've got the
tubes coming off of that and we already
have the tubes in the server room
already hooked up we had previously cut
a hole for our ducting solution so we
just stuffed the tubes down the duct
that goes through the like hallway there
into the Ser oh wow and these awesome
Cable Management things the magnet is so
strong that it just it's kind of
perfect in terms of pump this is not our
end game this is like a cast iron pump
and we're using oxyard tubing which it
limits the amount of oxygen it's
probably f look your house is probably
the same cast iron pump in it for like
20 years and it's fine but it isn't the
end game I picked up a stainless version
of the one step up from this pump this
one I think does around 20 gallons per
minute and the big boy that we're
getting does around 40 wow which is a
lot of gallons a lot of gallons per
minute okay are we ready to hook this up
in theory yeah I mean let's do it we
tried before so let's try again hold on
before you do that that tube is plugged
into the wrong thing on the top of that
oh did you guys anything right on the
first attempt or that is a excellent
question and we decided to not Mount the
filter up
there he always chirps me for doing
things like kind of the easy way and
then fixing it later and he's literally
just like purposely doing that right now
well we're just not going to fix it
later it's fine I'm going to fix it
later what no don't waste time on that
it's fine well you I'm not the one that
wasted time don't move it it doesn't
matter you told me it doesn't matter I'm
going to send you a video of me moving
it later no that is going to be a huge
waste of time cuz you'll have to
disconnect the tubes in order to you
could have just fixed it right now let's
put the tubes in come on I'm coming back
here with a rotary tool I'm actually
going to shave off the tops of these
screws let's give ourselves a little bit
of breathing a lot of breathing room
that's fine I like to breathe a lot we
we
know I plan to keep doing
it easy peasy by the way I found an
easier way to do this just take the
white thing out first oh okay okay this
is bothering me do you hear that now is
everyone hearing that I don't know what
you're talking about every just said
it's bothering me editor's note cut out
this entire story line okay it's on the
wall filtered what I dropped one of the
little shark bite white thingies and it
fell down the hole hey
lonus no you
suck oh my God Jake did you turn the
water on no why is it wet I don't
know where's the water shut off is this
valve broken
I I was dumping water down the hole oh
my God you suck do you want me to turn
the water on okay that actually does
pour down into an electrical box so you
really shouldn't do that oh what really
uh yeah I I honestly have no idea where
the shark bite thing went
taada what oh she's on no it's in it's
in somebody needs to go in the server
room and watch okay in case that leaks
because if that starts leaking it's
going to be a while before it all stops
leaking
ooh
dick ah a dick I get it no stop you a
his first is my loging in high school
was a. dick okay and then you want it
one click apparently right 7/8 inch
ballcock let's turn this thing on yeah
go for it see you later okay it's on I I
got water coming that's good do it full
send let's go I can't believe this tank
is not leak
are you ready Mr Dick I ready it's
coming whoa it sell fills how's it
looking why didn't we do this at my
house this is awesome no idea it's
actually great you know V2
right is it fine yeah like everything's
fine down there Jake we have a leak oh
God uh where uh on on the uh the return
fitting no we got it we got it I got it
I tell you guys standing right at the
back of the air output of these servers
it's
exhausting Alex Alex Alex he may be a
dick but he's our dick this is the
world's slowest leak at this point ready
one more and nice note that every
fitting I did is not leaking this is the
one you did I didn't do that one yeah
you did you stuck the tote I don't know
what you're talking about we managed to
fix our leaks I replaced the fittings
down here on both sides I think we just
used Too Much Teflon tape uh the first
time we hooked it up and it kind of just
like bunged up the threads and then
upstairs I just cut the PEX sanded it
down stuck it back in and everything's
good no more leaks now I've got the
million dollar PC hooked up and running
again and I want to test something
before Linus gets here uh one of the big
things you want to do in a setup like
this especially if you were doing this
in a data center is contain the hot air
so we're going to make ourselves a
little bit of a hot aisle with some
cardboard right now it says 31 is De on
the intake maybe it's 31.1 31.2
let's see if it goes up any Higher by
just adding the cardboard I want to just
kind of proof of concept before I spend
the time doing a better job of this
obviously still a giant Gap here but
let's see if it makes a difference oh
31.3 31.4 it's going
up5 6 okay maybe it's only like half a
degree but half a degree is important
because the whole game here is
temperature differential the larger we
can make the difference in temperature
on this side to the temperature out in
the warehouse the better this system
will work hey that's not
bad we have our hot aisle which is going
through the cooler and the rest of the
server room is our cold aisle it's not a
perfect science but it's better than
when it was
open oh oh god look I wanted optimal
circumstances for our very scientific
test it's definitely hot how do you like
it I have so many questions that's great
it's hot in here hey it's really hot hot
in here but would you believe me if I
told you the air conditioning's off
really it's 32° in here don't get me
wrong it is hot but the AC is off off
and this has been running for like hours
that's actually kind of cool so look at
the UPS we're drawing 4.95 Kow except no
we're not half of these servers are
hooked up to the Main's power so we're
probably drawing more like probably like
8 to 10 Kow however the can we turn the
AC on yes aren't we going to be taking
cold air that's been heated up a little
and running it through our heat
exchanger potentially cooling the
warehouse look I don't know if it's
going to get that cold uh I don't know
if you've stood Behind these things at
all they're hot it's quite hot the exit
temperature of these servers is probably
like 40° even with air condition air
coming through it but you are right it
will be colder that being said before
when these actually running with just
the air conditioning it was 40° in here
I think we should turn that off and see
how hot it gets in here okay cuz it's
been 32 for over an hour this is a cool
software called check MK it's a
monitoring tool that's open source very
awesome we've hooked up the systems with
SNMP which is a monitoring protocol and
you can see the coolant coming in is 28°
from coming from the warehouse yes after
it's been cooled with air that's around
21° and then and leaving here it's 32°
that's a 4° difference that's a lot of
heat it doesn't sound like a crazy
number but at the fluid flow rate that
we've got that's a freak ton of heat
yeah clearly we have a problem of it not
quite getting cooled over there as much
but I had a brilliant idea we have six
of the bloody things let's just put
another up there we could why not or
hear me out we bury a coil in the
parking lot oh I'm totally down for that
give me the approval I will find a
contractor today that is not that's
above my pay grade these days oh I got
to ask paren yes hi Money free cooling
lus said it was a good idea anyway yeah
we could throw another one up there for
sure like pretty easily we just actually
need two T's that's it interestingly too
the return versus Supply Air is a 3°
difference right now so the air coming
into the back is almost 40° 37 and then
the air coming out of the front is 33.6
they are still going up a bit but like I
said it's been at 30 2 for an hour uh I
imagine if we left this overnight we
probably come back and it might be like
34 or 35 in here but considering we're
not air conditioning this at all let's
see what happens if we turn it off oh
God I don't think the air conditioning
is going to make that much of a
difference in terms of the air coming
out of here the metal on the back of
this rack is up to
46° the air coming out of the back of
this power supply is as high as
60° oh 76 it's uh 33 .2 now this may not
be safe for this hardware for much
longer it's 33.3 now it's gone up a full
degree in like 3 minutes it's getting
warmer
34.1 I'm getting quite uncomfortable I
think what I want to see now is if the
air conditioner can actually work
cooperatively with the heat exchanger to
get it down to like normal temperature
in here yeah okay all right let's do it
so our Baseline is when we started this
project it was hitting about 40° in here
with just the air conditioner running if
we can beat that it means that somehow
through the magic of thermodynamics they
are working together 34 and2 plug the
goddamn thing back in
a sweet relief so our Peak was
42 with the AC off and now it's come
down
to
37 37.8 and up here is equally as mint
you like my sound ding yeah I mean it'll
do something not much in this config
that's what I was going for is something
something long term we get sheet of
plywood and attach the rock wall on the
inside of it to kind of make a baffle if
I stand here it's pretty loud but if I
go behind this
thing it's a pretty substantial
difference we just have to create kind
of a a sound blocking maze that air can
move through but um block sound from
reaching people below us and it's also
at like 80% fan right now if we put a
second one up here and run them like
half the speed should be tolerable all
right wait we should look at the filter
oh is there shoo in there not too bad
and we're back so not as good as it was
before no it says 1.8 th000 Watts on the
readout which oh no which is a lot given
the amount of power that we're putting
into it what one pump in some fans huh
22° in here right now Supply versus
return air is still like a Delta of more
than 2° that's solid
and interestingly the cooling
temperature is lower but what I realized
look at this the fan speed is lower oh
what I also realized after looking at
this is that there's a valve I remember
when you guys did the thread R cooling
there's a manual valve right that's like
the bypass valve and you guys were like
oh you're supposed to close it so it
doesn't bypass actually you're supposed
to leave it open because there's a
mixing valve in the unit for your
application actually probably just shut
it doesn't matter but the thing can
dynamically adjust how much water goes
through the radiator and how much gets
bypassed I think to maintain to maintain
a Delta ideal temperature yeah it's
totally fine in here now it's working
I'm surprised it works this well well
the ducting was key but the other big
thing is I think that we were just on
the edge of this air conditioning unit's
capacity so just taking the edge off
taking another thousand couple thousand
Watts out of here and what's cool is
because we've got it hooked up direct
directly to the exhaust from this rack
adding more to this rack is going to
increase that Inlet air temperature
which increases the efficiency of the
thermal transfer of our heat exchanger
mission accomplished yeah I'm actually
kind of shocked I mean 2° cut off the
exhaust temp doesn't sound like a lot
but that's like already outside of the
server and we're talking 2° and a lot of
air oh I can't wait for part two it's
going be so much better when this is
directly on the rack I'm thinking we put
two on the mezzanine for like winter
time but we could also put one like
outside somewhere we could have valves
and we could decide where we want to
dump heat from this room we could
automate them pretty easily too we got
have electric Valves and a couple temp
sensors and a Ras pie so we can send the
heat outside when it's hot in the
warehouse and send it inside when we
want to heat the warehouse yeah and
interestingly we could put it in that
mechanical room and just like cut a hole
in the one put a big thing yep it's our
mechanical one yeah what's the landlord
going to do about it screw that guy and
screw the segue to our sponsor
Squarespace creating your own website
doesn't have to be difficult and luckily
with Squarespace it isn't they're all in
one platform makes it easy to get your
website up and running quickly and
designing with their fluid engine site
Builder is easy it's so easy start with
a template and customize the details to
your heart's desire with intuitive drag
and drop elements on both desktop and
mobile you can also use their asset
library to manage all your files from
one Central Hub and use them across the
entire Squarespace platform plus with
squarespace's analytic insights you can
see what's working well and What needs a
little TLC just a little
bit you know and if you need help
Squarespace has got your back with
helpful guides and a 247 support team
they do not sleep head to
squarespace.com
and get 10% off today if you guys
enjoyed this video why not check out the
time we did this at home with radiators
from PT Cruisers oh yeah yeah this would
have worked a lot better yeah but those
work pretty good you could just take one
of these home no they work great I'm not
changing anything oh yeah okay ducting I
could duct to the PT Cruiser radiators
but that's all I would change oh my God
we're getting that elu like 1 M by 1 m x
1 M 3D printer and we have a 3D scanner
they could 3D scan the back of your rack
and make like a a duct shroud look he's
actually like considering it right now
you were thinking cardboard but we could
do it in here oh yeah totally cuz we
could take the AC straight to the front
of this rack we want some over here too
I guess if the ambient is low enough
it's probably fine it'll be fine yeah
okay
5.0 / 5 (0 votes)